Applying salt around earthing electrodes to help resolve neutral to ground line voltage issues
Vighnesh asked: Our neutral to earth voltage is fluctuating from 2.5v to 4.5v. We have a separate neutral earthing for UPS and DG and separate body earthing. We also regularly applying salt for earth pits but are unable to resolve our voltage issue. Can you please guide what we can do?
Vighnesh asked: Our neutral to earth voltage is fluctuating from 2.5v to 4.5v. We have a separate neutral earthing for UPS and DG and separate body earthing. We also regularly applying salt for earth pits but are unable to resolve our voltage issue. Can you please guide what we can do?
The Answer:
Generally speaking, reducing the resistance of the earthing electrodes (salting them) will not help you with a neutral to ground line voltage issue. First of all, you must have a common earthing electrode system as required under SP30: Section 14, which requires earth-continuity conductors between all electrode systems.
Now, how do you deal with the voltage? It is almost certainly caused by an erroneous neutral-to-earth bond somewhere in your system. Have you measured the amperage on your protective earthing (PE) system? You need to trace the current on your PE back to its source. No doubt, you will find a subpanel or backup generator somewhere that has a connection from neutral to earth that should not be there and is allowing normal operating neutral currents to travel back on the protective earthing system.
Related Articles

What to Look for When Choosing an Electrical Grounding Company
In the construction industry, selecting the right electrical grounding company is crucial for ensuring safety and project success. This blog post delves into the key factors you should consider to make an informed decision.
Read article
The Future of Electrical Grounding: Double Ring Electrode Systems
Inner Foundation Ring: Embedded within the concrete foundation, this ring bonds directly to the structural steel rebar, creating a unified grounding system throughout the building's foundation. Outer Buried Ring: Installed in direct contact with earth at a minimum depth of 0.5m (20 inches) and at least 1m (3 feet) from the foundation, this ring incorporates ground rods at strategic intervals and serves as the primary electrode system.
Read article
Expertise vs. Experience: What Truly Sets E&S Grounding Apart
At E&S Grounding Solutions, our 22+ years in business represent more than just longevity. They represent the expertise we've cultivated through tackling some of the most challenging engineering problems in grounding, earthing, and electrical safety. Our experience spans a broad range of industries and applications, including step and touch voltage assessments at substations, electromagnetic interference analyses for data centers, and specialized lightning risk assessments.
Read article